SF25 and SF35 Operating Instructions
|
 |
Safety Instructions
The following instructions are for ensuring the user’s safety and to prevent any physical injury or material
damage. Please read carefully and follow all instructions.
There are two sections to these instructions: WARNING and CAUTION.
WARNING
- Use a 230V, 50Hz, 1 phase power supply only (wrong supply may cause a fire and / or shock hazard
- Securely plug into an earthed supply (unless earthed, may cause electric shock)
- DO NOT use a damaged power cable, plug or socket (short, fire, or shock hazard)
- DO NOT remove the plug by pulling the cable or with wet hands (risk of fire and electric shock)
- Before cleaning, remove the plug from the socket (otherwise risk of electric shock)
- DO NOT place anything on top of the unit (this could cause electric shock, malfunction, or injury)
- DO NOT use an extension lead unless of the approved type (heavy duty, risk of fire and
/ or electric shock)
- Ensure mains plug is clean and securely plugged in (otherwise it may short causing smoke and fire)
- Ensure correct (13amp) fuse is fitted in the plug (otherwise malfunctioning or fire may result)
- DO NOT kink or sharply bend the power cable nor put any weight on it (the insulation may be damaged
causing fire and
/ or electric shock)
- DO NOT turn off by removing power plug. Always turn off at control panel first (risk of electric shock and
/ or malfunction)
- DO NOT use this cooler on unstable or inclined surfaces. Always use on a solid flat floor (risk of falling
causing injury, fire or malfunction)
Safety Notice
CAUTION
- DO NOT place cooler on uneven, unstable or inclines surfaces (this could cause malfunction)
- When storing the cooler, ensure that it is kept in a dry, cool place (to prevent corrosion and
malfunction)
- If not being used for some time, or if lightning is present, always unplug from the mains (to prevent risk
of electric shock, short circuit or fire)
- DO NOT spray water on to the cooler nor use solvents such as benzene, thinner or alcohol for cleaning
(there is a risk of electric shock and
/ or short circuit)
- If the power cable is damaged this must be replaced by a fully qualified electrician (to avoid danger of
electric shock, short circuit or fire)
General Advice before Use
- Ensure the safety of the location in which the cooler is to be used
- Ensure the floor or ground is smooth and sound
- Ensure you allow at least 50cm air space all around the cooler
- When in position LOCK the casters to prevent rolling
- Never use the cooler at more than 2° incline
FOR MAXIMUM EFFICIENCY
- In airtight areas use vertical exhaust ducting into ceiling
- If possible locate exhaust outlet through a window or door to outside
- Exhaust ducting should be no longer than 2m for maximum efficiency
- Ensure correct electricity supply
Control Panel Functions

- Power: Use to power On / Off
 : Raises or
lowers temperature and
/ or sleep (off) time
- Cool: Use to select cooling mode
- Low Mode: Controls fan low speed
- High Mode: Controls fan high speed
- Off timer: To set the length of time, once turned on, that you wish the cooler to run
for. You can set 0-24 hours. Time intervals are 30 minutes, up to 10 hours and then 1 hour between 10 and 24 hours.
- Remote: From the long distance, you can control the machine by wired remote control
- Room: If the LED light is ON, the displayed temperature is for Room Temp. If the LED
light is OFF the displayed temperature is for Spot Temp
- Comp: When the compressor is operating the LED light is ON
- Error: Error signal (E1 – High Pressure, E2 – Low Pressure, E3 – Sensor, AF – Eva Freezing)
- Water Full: Red Light indicates TANK FULL. The compressor will shut off automatically. Empty tank and
replace in position to resume operation
- Align Drain Tank: The red light indicates the water tank is not in the correct position
- Display: Display Room
/ Spot temperature and the setting temp and sleep time in case of setting them. When the user set the sleep timer, HR
will be turned on. (Display of LO – under 0°C, Display HI – over 50°C)
Operation
Running and Stop
- Start by pressing the POWER button
- Cooler will start up automatically
- To STOP the unit, press the POWER button once again
- To change the fan speed, press the LOW button
- If you wish to operate on fan only, press the COOL button, to resume cooling press the
COOL button again. (Note: There is a 3 minutes delay when switching functions to protect the compressor)
Selecting of Area / Room or Spot Cooling
To reduce the temperature of the entire room then select Room
/ Area Cooling. For targeted cooling of machinery, severs or people etc, select Spot Cooling.
- If you want to display the room temperature, then push COOL and
button
simultaneously for 3 seconds
- If you want to switch from Centigrade to Fahrenheit, then push UP
and DOWN buttons
simultaneously for 3 seconds
Temperature Control Operation
- When the power is on, the set temperature is displayed. Default of set temperature is
5°C
- When you push either up
or down buttons,
the setting temperature can be changed
- The display showing the set temperature will blink 3 times
- Limits of Room
/ Spot and Setting temperatures. Room Spot Temp 0-50°C the setting range will be 1°C – 30°C.
Cooling operates when Room / Spot temperature is more than the set temperature.
Cooling stops when the Room / Spot temperature is less than set temperatures.
How to set the Off Timer
This function enables you to set the length of time you want the cooler to operate. You can set the time period
from 30 minutes to 24 hours in 30 minutes and 1 hour increments.
- When the cooler is operating, press the OFF TIMER button and set the length of timer
you want by pressing
or . Each
time you press the button you will increase the TIME TO OFF period by 30 minutes, upto 10 hours, and 1 hour
thereafter up to 24 hours. The display will show .5 for 30 minutes and 1 for an hour, eg 1˝ hours will be shown as
1.5
- When you have finished setting the time period, the OFF TIMER lamp will illuminate,
which indicates the cooler is in sleep (off timer) mode
- If you press the OFF TIMER button during its operation, the remaining time will be
shown.
- To CANCEL timing, press OFF TIMER button for ONE second, it will switch the timer off
automatically.
Error and Warning Indicators
The units safety devise will automatically signal any problems via the display window on the control panel. The
information below shows how to read these signals:
- Water Full – Display Shows FU
When the water container is full, FU is displayed and the LED Water Full illuminates
- Align Water Tank
If the water tank is not positioned correctly, the LED Align Drain Tank will illuminate
- High Pressure
E1 is displayed and the Error will be on when the pressure of the compressor is too high and the high pressure
switch is open
- Low Pressure
E2 is displayed and the Error LED will be on when the pressure of the compressor is too low
- Sensor Problem
If the thermistor is short circuited or cut, E3 is displayed and the Error LED will be on
- Anti Freezing
When the temperature of the evaporator is below -4°C, AF is displayed and the Error LED will be on
Cleaning and Maintenance
Cleaning the Air Filters
- To remove filters, slide up a little the back panel and pull towards you
- Clean the filters with water and compressed air
- Clean evaporator and condenser units with a vacuum cleaner or compressed air
Maintenance
- After cleaning, completely dry the inside of the unit by operating on the FAN MODE only
for 3-4 hours
- Turn OFF at control panel, remove plug from socket, coil and store cable neatly
- Keep the unit suitably covered to prevent damage by damp, humidity and dust
Trouble Shooting
|
Trouble
|
Check
|
Remedy
|
|
Not Working
|
Power plug correctly connected
|
Connect plug correctly
|
|
POWER button OFF
|
Press POWER button to ON
|
|
Blown fuse in mains plug
|
Replace fuse (MUST BE 13amp)
|
|
Fuse (supply) blown
|
Exchange fuse board
|
|
Breaker on switch board tripped
|
Check load capacity and reset
|
|
Ambient temperature too high
|
Use only below 45°C (HSC-3500:40°C)
|
|
Poor Cooling
|
Filter blocked with dust
|
Clean filter
|
|
Dust in heat exchanger
|
Clean heat exchanger
|
|
Obstacle against inlet side
|
Remove and allow 50cm clearance
|
|
Ambient temperature too high
|
Use only below 45°C (HSC-3500:40°C)
|
|
E1 High Pressure
|
Exhaust fan is not operating
|
Check the power supply or Call London Cool on 0800 440 444 for motor replacement
|
| |
Hot air being restricted from leaving the machine
|
Unblock or relocate exhaust hose
|
|
E2 Low Pressure
|
Refrigerant is leaking. Check with manifold gauge
|
Call London Cool on 0800 440 444
|
|
E3 Sensor Problem
|
Thermister sensor wire cut
|
Change the thermistor sensor
|
|
AF Anti Freezing
|
Evaporator is frozen. (Ambient temp is under 20°C)
|
Operate continuously until AF disappears or operate in FAN mode
|
If problems persist, call London Cool on 0800 440 444
|